This paper introduces an original approach for the evaluation of the cooling load due to the solar radiation incident on the glazed surface of a building. This approach is based on a newly introduced parameter called Solar Response Factor, defined as the overall convective heat flux released by the building envelope to the indoor space per unit radiant heat flux acting on the outer surface of the glazing. The Solar Response Factor is a complex number, and can be calculated as a combination of the thermal and the optical properties of walls and glazing. In particular, the paper discusses how the Solar Response Factor depends on the optical properties of the envelope, on the size of the windows and on the type of walls delimiting the enclosed space. Furthermore, under steady-periodic conditions, the use of the Solar Response Factor allows an easy analytical estimation of the cooling load due to solar gains. The reliability of this approach is successfully proven by comparison with a series of simulations carried out with EnergyPlus. The results provide very useful information for optimizing the thermal response of an enclosure to periodic solar heat gains.

The solar response factor to calculate the cooling load induced by solar gains

EVOLA G
;
MARLETTA L
2015-01-01

Abstract

This paper introduces an original approach for the evaluation of the cooling load due to the solar radiation incident on the glazed surface of a building. This approach is based on a newly introduced parameter called Solar Response Factor, defined as the overall convective heat flux released by the building envelope to the indoor space per unit radiant heat flux acting on the outer surface of the glazing. The Solar Response Factor is a complex number, and can be calculated as a combination of the thermal and the optical properties of walls and glazing. In particular, the paper discusses how the Solar Response Factor depends on the optical properties of the envelope, on the size of the windows and on the type of walls delimiting the enclosed space. Furthermore, under steady-periodic conditions, the use of the Solar Response Factor allows an easy analytical estimation of the cooling load due to solar gains. The reliability of this approach is successfully proven by comparison with a series of simulations carried out with EnergyPlus. The results provide very useful information for optimizing the thermal response of an enclosure to periodic solar heat gains.
2015
cooling load; Solar gains; Glazed Envelope; Thermal inertia
File in questo prodotto:
File Dimensione Formato  
2015_APEN.pdf

solo gestori archivio

Tipologia: Versione Editoriale (PDF)
Licenza: Non specificato
Dimensione 974.28 kB
Formato Adobe PDF
974.28 kB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.11769/18044
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 14
  • ???jsp.display-item.citation.isi??? 13
social impact