This paper investigates the microclimate in a conference room with thermal stratification, taking as a case study the chapel of Villa San Saverio, now the seat of the “Scuola Superiore” of the University of Catania (Italy). Surveys of the former chapel were conducted to monitor air temperature and relative humidity. Subsequently, the investigation relied on numerical simulations of a simplified computational fluid dynamics (CFD) model built with the DesignBuilder v7.0 software and validated by comparison with measured values. Simulations were then carried out considering three different scenarios: the current state without any HVAC system and two possible HVAC system configurations providing both air conditioning and ventilation. The results show that, from a comfort perspective, a lightweight radiant floor heating system, assisted by an appropriate ventilation system for air renewal placed at the floor level near the occupants, is preferable to floor-level fan coils and high ventilation channels. Furthermore, this was also confirmed by a preliminary energy analysis of the two HVAC options, where the ventilation effectiveness of the winter period, the temperature of the water the emitters are fed, the consequent COP value of the heat pump, and the electricity consumption were taken into consideration.

Microclimate Investigation in a Conference Room with Thermal Stratification: An Investigation of Different Air Conditioning Systems

Andrea Longhitano
Primo
Membro del Collaboration Group
;
Vincenzo Costanzo
Secondo
Membro del Collaboration Group
;
Gianpiero Evola
Penultimo
Membro del Collaboration Group
;
Francesco Nocera
Ultimo
Membro del Collaboration Group
2024-01-01

Abstract

This paper investigates the microclimate in a conference room with thermal stratification, taking as a case study the chapel of Villa San Saverio, now the seat of the “Scuola Superiore” of the University of Catania (Italy). Surveys of the former chapel were conducted to monitor air temperature and relative humidity. Subsequently, the investigation relied on numerical simulations of a simplified computational fluid dynamics (CFD) model built with the DesignBuilder v7.0 software and validated by comparison with measured values. Simulations were then carried out considering three different scenarios: the current state without any HVAC system and two possible HVAC system configurations providing both air conditioning and ventilation. The results show that, from a comfort perspective, a lightweight radiant floor heating system, assisted by an appropriate ventilation system for air renewal placed at the floor level near the occupants, is preferable to floor-level fan coils and high ventilation channels. Furthermore, this was also confirmed by a preliminary energy analysis of the two HVAC options, where the ventilation effectiveness of the winter period, the temperature of the water the emitters are fed, the consequent COP value of the heat pump, and the electricity consumption were taken into consideration.
2024
thermal comfort, thermal stratification, historic building, radiant floor, ventilation
File in questo prodotto:
File Dimensione Formato  
Longhitano et al - 2024 - Microclimate Investigation in a Conference Room.pdf

accesso aperto

Tipologia: Versione Editoriale (PDF)
Licenza: Creative commons
Dimensione 7.14 MB
Formato Adobe PDF
7.14 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.11769/596122
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact